Heat recovery ventilation: electrical supply, control and KNX
A heat recovery ventilation (MVHR) system is designed and installed by the HVAC specialist, but the unit needs power, the control panels need cables and the smart home needs data. This article covers the electrical side: what supply the unit needs, where the controls go, and how a Zehnder ComfoAir Q is integrated into KNX so that bathroom humidity or bedroom CO₂ raises the airflow on its own.
In short
- Who does what: the ventilation system (design, unit, ducting, commissioning, service) comes from our Zehnder dealer partner, Energetika 2020 Kft.; the unit’s power supply, the control cabling and the KNX integration are our job.
- Supply: according to the ComfoAir Q350 data sheet, 230 V single-phase; maximum power is 1850 W with the pre-heater and 180 W without. The circuit must be sized for the pre-heater too.
- Controls: Zehnder wall controls take their extra-low-voltage supply from the unit’s ComfoNet connector, over a 4-core cable up to 50 m. The cable must be in before plastering.
- KNX: the ComfoConnect KNX C module connects to the ComfoNet bus; ventilation level, boost and away mode can be set from KNX, and temperature, humidity and filter data are visible on KNX.
- Sensors: up to 8 bedroom and 8 other-room CO₂ sensors and 8 bathroom humidity sensors can be linked, raising the airflow automatically.
Author: Norbert Madarász
, Managing Director and Partner · Updated: 11 November 2026
Who does what in a heat recovery ventilation system?
A heat recovery ventilation system consists of the unit, the duct network, supply and extract valves and the controls. Designing and installing ventilation is an HVAC trade; the electrician comes in wherever power, cables or a bus are needed.
| Task | Who |
|---|---|
| Airflow calculation, unit selection, duct design | Energetika 2020 Kft. (Zehnder dealer) |
| Supply and installation of unit, ducts and valves | Energetika 2020 Kft. |
| Commissioning, balancing, filters and service | Energetika 2020 Kft. (Zehnder service centre) |
| Unit power supply, dedicated circuit, protection | MDRSZ Elektro |
| Cabling for controls and sensors, conduits before plastering | MDRSZ Elektro |
| KNX integration: ComfoConnect KNX C, ETS programming, visualisation | MDRSZ Elektro |
Our partner Energetika 2020 Kft. (Szilárd Papp) has designed, installed and sold Zehnder ventilation systems since 2013, has been a Zehnder service centre since 2019, and is listed among Zehnder’s Hungarian dealers. Services: szellozes.info; Zehnder products: szellozes.net (both in Hungarian). Ventilation design and installation for family houses: heat recovery ventilation at MDRSZ Bau.
What power supply does a heat recovery unit need?
The two fans draw little power, but the supply still cannot come from “any socket”. According to the manufacturer’s data sheet, the Zehnder ComfoAir Q350:
| Data (ComfoAir Q350) | With pre-heater | Without pre-heater |
|---|---|---|
| Supply voltage | 230 V, single-phase, 50 Hz | 230 V, single-phase, 50 Hz |
| Maximum power consumption | 1850 W | 180 W |
| Current draw | 10.0 A | 1.42 A |
| Fuse rating | 10 A | 3 A |
| Pre-heater power | 1.7 kW | – |
The difference is the electric pre-heater, which warms the incoming outdoor air in cold weather so the heat exchanger does not freeze. If the unit has a pre-heater, the supply must be designed for 10 A, which means a dedicated circuit in the plant room. Other models (ComfoAir Q450, Q600 or other makers) differ, so we always size the supply from the actual unit’s data sheet.
- Dedicated circuit: circuit breaker with the rating the manufacturer specifies, with an RCD, according to the unit’s installation manual.
- Location: the unit usually goes into the plant room, loft or a storeroom. We match the outlet position to the HVAC duct plan so the supply does not end up behind the unit or in the path of the condensate drain.
- Later accessories: if a cooling or heating module may be added later, its supply is marked in the design in advance.
Controls and ventilation control without KNX
The Zehnder ComfoAir Q talks to its controls and accessories on its own bus (ComfoNet). According to the data sheet, the ComfoSwitch C and ComfoSense C wall controls are four-position switches (four selectable airflow settings), take their extra-low-voltage supply directly from the unit’s ComfoNet connector, are IP44, flush- or surface-mounted, and are connected with a 4-core cable of up to 1 mm², up to 50 m.
- Where should the control go? Where people want to adjust ventilation: the living room, near the kitchen, and often next to the bathroom where boost is needed.
- Cable before plastering: the control cable runs to the unit, so conduit and box must be planned before bricklaying or prefabrication. Afterwards it means opening walls.
- From the phone: the manufacturer’s ComfoConnect LAN C module connects the unit to the home network for app control. This needs a network cable to the plant room.
KNX integration: what can the Zehnder ComfoConnect KNX C do?
The ComfoConnect KNX C is the manufacturer’s interface between ComfoNet and KNX. According to its manual it works with the ComfoAir Q, Comfort Vent Q and AERISnext units, is wall-mounted, preferably near the unit, is powered from the unit via the 4-core ComfoNet cable (+12 V DC), and only one per ComfoNet bus is allowed. On the KNX side it connects to the TP bus and is programmed with ETS.
| Function from KNX | What it means in practice |
|---|---|
| Ventilation level (0–3), away | The “away” button or the house mode also puts ventilation on the lowest level. |
| Boost with adjustable duration | After a shower, cooking or guests, airflow goes to maximum temporarily from a button or a sensor. |
| Auto or manual mode | In auto mode the unit runs its own schedule and KNX only observes; in manual mode KNX sets the level and setpoint and the unit’s internal schedule is disabled. |
| Temperature profile, external setpoint | The unit can temper the incoming air; the setpoint can come from KNX. |
| Temperature and humidity | Outdoor, supply, extract and exhaust air temperature and humidity on the visualisation. |
| Error, filter change | Error flag, hours until filter change and “filter dirty” status, shown on a KNX display or phone. |
The most useful part is the sensor input: values from KNX CO₂ and humidity sensors go straight to the unit, which then runs at least at a given level. Thresholds according to the manual:
| Sensor (up to 8 rooms each) | Threshold | Minimum level |
|---|---|---|
| CO₂, bedroom | below 800 ppm / from 800 ppm | 1 / 2 |
| CO₂, other room | below 800 ppm / 800–1200 ppm / from 1200 ppm | 1 / 2 / 3 |
| Humidity, bathroom | below 35% / from 35% | 1 / 2 |
What is worth automating in KNX?
- Bathroom: a humidity sensor in the KNX push button or ceiling raises airflow after a shower, with no separate extractor fan.
- Bedroom: with a CO₂ sensor ventilation only runs harder at night when really needed, so it is quieter and removes less heat.
- Away and holidays: the house “away” scene turns down ventilation together with lighting, heating and shading.
- Filter change: the filter alert appears on the KNX visualisation or as a message instead of getting lost on the plant-room display.
- With heating: room heating control and ventilation run in one system. See: smart thermostat and room-by-room heating control.
Our managing director has also completed the KNX HVAC Specialist course on heating, cooling and ventilation control, so we design the KNX side of ventilation together with heating and shading. More: KNX smart home.
What to decide before bricklaying and plastering
- Unit location and model from the HVAC design: this sets the supply size (with or without pre-heater).
- Dedicated circuit to the plant room, sized in the electrical design.
- Control positions, with a 4-core cable and conduit to the unit (up to 50 m).
- KNX bus to the plant room for the ComfoConnect KNX C, and positions of CO₂ and humidity sensors in bedrooms and bathrooms.
- Network cable to the unit if it will be controlled from an app or a LAN C module is added for firmware updates.
Related: Electrical design · KNX smart home · Heat pump and solar connection · Low-voltage systems
Frequently asked questions
Does a heat recovery unit need a dedicated circuit?
It is advisable. According to the ComfoAir Q350 data sheet the unit draws up to 1850 W with the pre-heater (10.0 A, 10 A fuse) and 180 W without. We design the supply from the actual unit’s data sheet, with a dedicated circuit and RCD.
Can a Zehnder ventilation unit be connected to KNX?
Yes, with the manufacturer’s ComfoConnect KNX C module for ComfoAir Q, Comfort Vent Q and AERISnext units. Ventilation level, boost and away can be set from KNX, and temperature, humidity, error and filter data can be read.
What cable does the ventilation control need?
The Zehnder ComfoSwitch C and ComfoSense C controls are connected to the unit with a 4-core cable of up to 1 mm², up to 50 m, which also powers them. Cable and conduit must be installed before plastering.
Can ventilation be controlled by CO₂ or humidity?
Yes. Up to 8 bedroom and 8 other CO₂ sensors and 8 bathroom humidity sensors can be linked to the ComfoConnect KNX C via KNX; the unit then runs at least at the given level (for example level 2 from 800 ppm in a bedroom).
Who designs and installs the ventilation system?
Our Zehnder dealer partner, Energetika 2020 Kft., designs, supplies, installs, commissions and services the system. We do the power supply, control and sensor cabling and KNX integration.
Let’s talk about your project.
Tell us what you are planning and we will get back to you within a few days.
Get in touch