Emergency lighting in Hungary: where it is required and how it is tested
Emergency lighting – in Hungarian legal terms safety lighting and escape signs – keeps escape routes and exits lit during a power failure. Where it is required is set by the Hungarian National Fire Protection Regulation (OTSZ), based on the building’s risk class and use; a family house generally has no such requirement. Where it is required, the operator must check it every three months, have it inspected every year, and record everything in the operating log.
In short
- Where is it required? Under § 146 of the OTSZ, among others on escape routes of medium (KK) and high (MK) risk-class buildings, in nurseries and schools, and in rooms for large gatherings. In workplaces, the occupational safety decree also requires it on emergency escape routes.
- How long must it last? Under the OTSZ, 30, 60 or 90 minutes depending on risk class; the exact value is set in the fire safety design.
- How often is it tested? Operator check every 3 months, periodic inspection and maintenance every 12 months, both recorded in the fire safety operating log.
- Who is responsible? The operator. Inspection and maintenance are carried out by a suitably qualified “authorised person” appointed by the operator.
Author: Norbert Madarász
, Managing Director and Partner · Updated: 8 November 2026
What is emergency lighting, and what types are there?
Emergency lighting is lighting that comes on when the supply to normal lighting fails. The part of it that serves escape is emergency escape lighting (Hungarian: biztonsági világítás). The OTSZ and the related Fire Protection Technical Guideline (TvMI) distinguish the following:
| Type | Purpose | Typical location |
|---|---|---|
| Escape route lighting | lights corridors, stairs and exits so the building can be left safely | escape routes, stairwells |
| Escape sign (externally or internally illuminated) | shows the exit and the direction of escape with a pictogram | above exit doors, at every change of direction |
| Anti-panic (open area) lighting | gives enough light in large spaces for people to reach a point from which an escape route is visible | rooms for large gatherings, halls |
| Low-mounted escape route guidance system | markings near floor level supplementing the high-mounted signs | where the regulation or the authority requires it, e.g. because of smoke |
| Dynamic escape sign | changes the indicated direction depending on where the fire is | recommended by the TvMI for multi-directional evacuation |
The Hungarian term irányfény (direction light), still common in older buildings, refers to direction lighting under earlier rules; the OTSZ inspection table still lists it alongside safety lighting.
Where is emergency lighting required?
Emergency lighting is required where the OTSZ, occupational safety rules or the fire authority require it. Under § 146 of the OTSZ, escape lighting must be installed, among others:
- on escape routes of KK and MK (medium and high) risk-class buildings,
- on escape routes of nurseries, schools, child welfare and childcare institutions,
- in rooms for large gatherings,
- in rooms and routes used by the fire brigade: fire alarm control room, fire main switch, firefighting lift lobby, temporary refuge.
Escape signs – illuminated, high- or mid-mounted – are required on escape routes of AK, KK and MK class buildings and in rooms with a capacity above 100 people. Anti-panic lighting is required in rooms for large gatherings and in rooms for people who cannot be evacuated, or only after preparation (such as bedridden patients).
Risk class: what decides it?
The risk class is determined by the fire protection designer. Under Annex 1 of the OTSZ, the factors include:
| Factor | NAK | AK | KK | MK |
|---|---|---|---|---|
| Height difference between exit level and highest relevant floor | 0–7 m | 7–14 m | 14–30 m | over 30 m |
| Capacity of the largest room | 1–50 | over 50 | over 300, as a dense crowd | – |
| Ability of occupants to escape | unaided | with assistance | can be evacuated without preparation | only with preparation, or not at all |
Family house: a single-storey or two-storey family house is typically in the lowest class (NAK), for which the OTSZ does not require emergency lighting. Apartment building: it depends on height. In taller buildings escape signs in the stairwell may be mandatory, in even taller ones escape lighting too; the building’s fire safety documentation states which. Workplace: Decree 3/2002 (II. 8.) SzCsM–EüM requires emergency escape routes and doors to have emergency lighting that works during a power cut, and automatic safety lighting wherever a sudden loss of lighting could endanger workers.
How long must emergency lighting last?
Annex 11 of the OTSZ ties the required operating time of safety lighting in a fire to the risk class: NAK and AK: 30 minutes, KK: 60 minutes, MK: 90 minutes. Under § 137, the shorter of this and the fire resistance requirement of the load-bearing walls applies; the specific value is fixed in the fire safety design.
- Changeover: with a central safety power source, switching from normal to safety supply may take at most 1 second for safety lighting (OTSZ § 137).
- Partial failure: according to the TvMI, safety lighting must also switch on when a single lighting circuit fails, not only the whole supply. This needs voltage monitoring, auxiliary contacts on the circuit breakers, or a suitably placed branch circuit.
- Luminaires: manufacturers typically offer 1-hour and 3-hour rated versions. The design sets the required value; as the battery ages the real duration drops, which is why regular testing is needed.
What do the standards require for illuminance and signs?
Photometric requirements are in MSZ EN 1838, luminaires are covered by MSZ EN 60598-2-22, and system design and testing by MSZ EN 50172. The TvMI says the current edition must always be used; the European editions of EN 1838 and EN 50172 were revised in 2024.
- Escape route: on routes up to 2 m wide, at least 1 lux at floor level, with a maximum-to-minimum ratio of no more than 40:1. The 2013 edition required this along the centre line; the 2024 edition extends it across the route width.
- Escape sign: the sign’s luminance must still exceed 2 cd/m² at the end of the required operating time (TvMI 12.2.1), and the pictogram must clearly show the direction.
- Anti-panic lighting: under MSZ EN 50172 it is also needed in halls and spaces larger than 60 m², in parts not marked as exit routes (TvMI 12.4).
- Placement (OTSZ §§ 152–153): the sign goes above the exit door, not on it; a sign is needed at every change of direction, and at least one must be visible from any point. Where people do not know the building, signs stay lit throughout the period of use (§ 146 (4)).
Central battery or self-contained emergency lighting?
An emergency lighting system can get its back-up supply in two ways: each luminaire has its own battery, or a central battery unit supplies the luminaires.
| Aspect | Self-contained luminaire | Central battery system |
|---|---|---|
| Cabling | standard cable is enough: under OTSZ § 138 the power source is inside the luminaire, so fire protection of the wiring is not needed | within a fire compartment, a cable system that keeps working in a fire is required (TvMI 12.3.5) |
| Testing | luminaire by luminaire; simplified with an automatic self-test | centrally, in one place |
| Battery replacement | many small batteries, one per luminaire | one battery bank |
| Typical use (TvMI 12.3.4) | smaller systems; above 50 luminaires central monitoring is recommended | recommended above 100 luminaires for cost and monitoring reasons |
A general lighting luminaire can also serve as a safety luminaire if it is made as a single product with a built-in battery, or is supplied from a central battery system (TvMI 12.7). The number of luminaires per central circuit is limited by MSZ HD 60364-5-56.
How often must emergency lighting be tested?
Under Annex 18 of the OTSZ, safety lighting, illuminated escape signs and old direction lighting must be checked every 3 months, inspected every 12 months, and maintained at the time of the inspection. Each is recorded in the fire safety operating log.
| Activity | Interval | Carried out by | What it means |
|---|---|---|---|
| Operator check | every 3 months | the operator or their appointee | visual check: is the luminaire or sign in place, undamaged, visible, and what do the status indicators show (OTSZ § 249) |
| Periodic inspection | every 12 months (+1 month) | authorised person | practical test, measurement and dismantling if needed, review of the check records (§ 250) |
| Maintenance | together with the inspection | authorised person | tasks set by the manufacturer, e.g. battery and lamp replacement |
| Extraordinary inspection | within 15 days | authorised person | if the system failed during a fire, a drill or another event (§ 248 (3)) |
An automatic test system can replace the operator check if it tests at the required interval and records the result in a form that can be shown to the authority (§ 249 (3)). MSZ EN 50172 also includes more frequent short function tests and an annual test over the full rated duration; these are worth building into the inspection routine. The manufacturer’s instructions must be followed in every check (§ 248 (5)).
Who may test emergency lighting?
The operator is responsible. Inspection and maintenance are carried out by an authorised person under the OTSZ: someone appointed by the operator who has the necessary qualification, tools and experience. The list of jobs requiring a fire safety qualification exam (Decree 45/2011 BM) does not name emergency lighting separately; which qualification a given building needs is best clarified with a fire protection professional.
What goes into the emergency lighting log book?
In practice the emergency lighting log is the relevant part of the fire safety operating log. It may be kept on paper or electronically (OTSZ § 248 (4)). It should record:
- the date and the person carrying out each check, inspection and maintenance,
- the luminaires and signs tested (by their design reference),
- test results, including the measured duration,
- any faults found, and when they were fixed.
Faults are fixed according to their severity; anything that hinders escape must be repaired without delay (§ 251). During repairs the operator must compensate for the reduced protection by other means (§ 252). During refurbishment, escape signs pointing the wrong way must be switched off (§ 200 (4)).
How is an emergency lighting system installed?
- Requirements The fire safety design or consultant states where escape lighting, escape signs and anti-panic lighting are needed, and for how long.
- Electrical design Selection and positioning of luminaires, self-contained or central battery, circuits and cabling.
- Installation Mounting and connecting luminaires and signs, wiring for partial-failure detection.
- Commissioning and handover Function test, measurement, handover documents, and the log opened with its first entry.
We install emergency lighting systems in new and existing buildings, replace luminaires, and test systems and repair faults. We quote on the basis of the design or a site survey. If the condition of the building’s electrical installation is also in question, we can carry out an electrical safety inspection on the same visit.
More: LED lighting and lighting control · Electrical safety inspection · Electrical installation
Frequently asked questions
Where is emergency lighting required in Hungary?
Where the OTSZ requires it: among others on escape routes of medium and high risk-class buildings, in nurseries, schools and rooms for large gatherings; escape signs from the low risk class upwards and in rooms for more than 100 people. In workplaces, the occupational safety decree also requires it on emergency escape routes.
Is emergency lighting required in a family house?
Generally not. A family house is typically in the lowest risk class (NAK), for which the OTSZ does not require safety lighting. It can of course be installed voluntarily.
How often must emergency lighting be tested?
Under Annex 18 of the OTSZ: an operator check every 3 months, periodic inspection and maintenance every 12 months, with results recorded in the fire safety operating log.
How long must emergency lighting work?
Under the OTSZ, 30, 60 or 90 minutes depending on the risk class. The exact value is set in the fire safety design.
Who is responsible for emergency lighting?
The building operator. They arrange checks, inspection, maintenance and repairs, and have the inspection carried out by a suitably qualified authorised person.
What is the difference between emergency lighting and escape signs?
Escape lighting lights the escape route; escape signs show the exit and the direction of travel. Most buildings need both, often in one system.