Circuit breakers and surge arresters: B or C, 6 or 10 kA, T1 or T2 – and which brand?

Three kinds of protection work in a distribution board: the miniature circuit breaker (MCB) protects the cable against overload and short circuit, the RCD protects people against electric shock, and the surge protective device protects equipment against lightning and switching surges. This article explains the first and the third: what C16 and 6000 mean, how MCBs are sized, when a T1+T2 arrester is needed, and what to look for between brands.

In short

  • C16: C curve, 16 A rated current. The letter tells you at what current it trips instantly: B at 3–5×, C at 5–10×, D at 10–20× the rated current (EN 60898-1).
  • 6000 in a rectangle: 6 kA breaking capacity. The required value depends on the local short-circuit current.
  • Sizing: the MCB protects the cable, not the appliance. Its rating must not exceed what the cable can carry continuously for its installation method.
  • Surge arrester: with a lightning protection system, an overhead supply or a large metal object on the roof, T1+T2 at the supply, T2 in sub-boards, T3 at sensitive equipment.
  • Brand: what matters is the datasheet (curve, In, Icn, poles) and that it fits the busbar system of the board.

Author: Norbert Madarász, Managing Director and Partner · Updated: 11 November 2026

What do C16 and 6000 mean on an MCB?

An MCB trips in two ways: with a delay on overload (thermal release) and instantly on short circuit (magnetic release). The curve letter gives the instantaneous range as a multiple of the rated current (In).

B, C or D: when does it trip instantly?0×3×5×10×20×multiple of the rated current (In)Blighting, socket circuits at homeCmotors, pumps, higher inrushDtransformers, high starting currentMarking on the device:C166000C16 = C curve, 16 A6000 = 6 kA breaking capacity
An MCB trips with a delay on overload and instantly on short circuit. The instantaneous range depends on the curve (EN 60898-1). The number in the rectangle is the breaking capacity in amps.
MarkingInstantaneous tripTypical use
B (e.g. B16)3–5 × Inlighting and socket circuits, longer cable runs
C (e.g. C16)5–10 × Inmotors, pumps, appliances with higher inrush
D10–20 × Intransformers, machines with high starting current
6000 (in a rectangle)–breaking capacity: 6 kA; 4.5 kA and 10 kA versions also exist

Siemens’ 5SL6 range, for example, comes with B and C curves from 0.3 to 63 A and a 6 kA breaking capacity (EN 60898). Whether a circuit needs B or C, and whether 6 kA is enough, is decided by the design: the breaker must trip reliably at the far end of the cable, and its breaking capacity must not be lower than the short-circuit current expected at the installation point.

Sizing an MCB: what does it actually protect?

The MCB protects the cable from overheating. The HD 60364-4-43 rule, simply put: design current ≤ MCB rating ≤ the cable’s continuous current capacity. That capacity depends not only on the cross-section but also on the installation method and surroundings: in a wall, in insulation, in conduit or bundled, a cable carries less.

  • A bigger breaker is not the fix for a circuit that trips often: the circuit is overloaded or faulty. The answer is a new circuit or spreading the load.
  • Wiring an MCB happens in the board, close to live parts; a wrong connection disables the protection. It is electrician’s work, followed by testing.
  • Smart (Wi-Fi) breakers and energy meters exist. For remote switching and metering of a circuit, KNX or submetering also works: submeters and energy metering.

MCB brands: Schneider, Hager, ABB, Siemens, Eaton, Legrand

For residential buildings every major manufacturer offers 6 kA MCBs to EN 60898-1. A few examples from manufacturer and distributor datasheets:

ManufacturerExample (per datasheet)
Schneider ElectricResi9: 1P, B curve, 6 kA (EN 60898-1)
HagerMBN: B curve, 6 kA (EN 60898-1), 1P, 1P+N, 2P, 3P
ABBSH200: 6 kA; the 10 kA version is a separate series
Siemens5SL6: B and C, 0.3–63 A, 6 kA (EN 60898)
Eaton, Legrand, Schrack, Traconalso offer residential MCBs; we select the specific type by its datasheet

The brand is not what decides, the datasheet is: curve, rated current, breaking capacity, number of poles, and whether the device fits the busbar of the board and the RCDs next to it. That is why it pays to use one manufacturer within one board. We work with Schneider, Legrand, Hager, ABB, Eaton and Siemens devices.

RCD types (A, F, B, A-EV) have their own article: RCD types.

Surge arrester: T1, T2 or T3?

Under EN 61643-11, surge protective devices (SPDs) fall into three types. A T1 (type 1) lightning current arrester also discharges part of a direct lightning current, a T2 limits surges at the supply and in sub-boards, and a T3 protects close to sensitive equipment.

According to DEHN’s guidance for family houses, if the building has an overhead supply, an external lightning protection system, a large metal object on the roof (such as an aerial), or any of these applies to a neighbouring building, then at least a type 1 lightning current arrester belongs in the power supply. In most cases the manufacturer recommends a combined type 1+2 arrester with a 1.5 kV protection level and at least 12.5 kA lightning current capacity per pole (HD 60364-4-443).

Surge protection in stagessupplyoverhead line or cablemain boardT1+T2 (type 1+2)sub-boardT2 (type 2)sensitive deviceT3 (type 3)lightning current arrester if there isa lightning system or overhead linewithin the cable lengthadapter, socketUp ≤ 1.5 kV recommendedlow-voltage lines (aerial, phone, data) need protection too
According to DEHN’s guidance for family houses, with a lightning protection system, an overhead supply or a large metal object on the roof, at least a type 1, preferably a combined type 1+2 arrester belongs at the supply, with a 1.5 kV protection level.
  • Where it goes: according to DEHN, preferably before the meter, in the unmetered section; if that is not possible, as close as possible to where the metered main cable enters the building. The utility’s rules also set the conditions.
  • Earthing: a short bonding conductor to the main earthing terminal, at least 16 mm² for copper.
  • When one stage is enough: if the equipment to protect is within 5 m of cable from the arrester. Further away, add T2 in the sub-board and T3 at the device.
  • Low-voltage lines too: aerial, phone and data lines also need arresters near their entry into the building.

Surge protection brands: DEHN, OBO, Schneider, Hager

Surge arresters are offered by lightning protection specialists (such as DEHN and OBO Bettermann) and by switchgear makers (Schneider, Hager, ABB, Legrand, Tracon and others). What matters is the type (T1, T1+T2, T2, T3), the system (TN-C, TN-S, TT), the protection level (Up), the discharge capacity and the backup fuse – all on the datasheet.

Whether a house needs a T1 arrester depends on the lightning risk and the type of supply. We decide this in the design or on site; it can be retrofitted into an existing board if there is space and the earthing is adequate.

What to ask your electrician for

  1. A circuit schedule: which breaker protects which circuit, with what curve and rating.
  2. Properly sized circuits: the breaker must match the cable’s cross-section and installation method.
  3. Surge protection of the right type: T1+T2 at the supply where the conditions call for it.
  4. One system in the board: devices from one manufacturer on a busbar, with spare space for later.
  5. Testing and a report: loop impedance, insulation resistance, RCD tripping.
On replacing a consumer unit or building a new board: distribution board manufacturing. On the full installation: electrical installation.

Frequently asked questions

Do I need a B or a C breaker?

At home, lighting and socket circuits are typically B or C; C suits appliances with higher inrush (motors, pumps). The design decides, because the breaker must trip reliably at the far end of the cable.

What does 6000 on an MCB mean?

The number in a rectangle is the breaking capacity in amps: 6000 = 6 kA. It must not be lower than the short-circuit current expected at the installation point.

Can I replace a 16 A breaker with a 20 A one if it trips often?

No. The breaker protects the cable; if the cable is rated for 16 A, it can overheat behind a bigger breaker. Frequent tripping means overload or a fault, which must be investigated.

Does a family house need a surge arrester?

According to DEHN, with an overhead supply, a lightning protection system or a large metal object on the roof, at least a type 1, preferably a combined type 1+2 arrester belongs at the supply. A type 3 arrester is also recommended for sensitive equipment.

What is the difference between T1, T2 and T3 arresters?

T1 is a lightning current arrester for the supply, T2 is for the main board and sub-boards, T3 goes close to the equipment. A combined T1+T2 does the first two jobs in one device at the supply.

Which MCB brand is best?

The major manufacturers (Schneider, Hager, ABB, Siemens, Eaton, Legrand) all offer standard 6 kA residential MCBs. What counts is the datasheet and a consistent system within one board.