WAGO connector or terminal block? Wire joints in junction boxes and distribution boards
Wires in the wall have to be joined somewhere: in a junction box, at a light, in the board. Today this is mostly done with spring or lever connectors (in Hungary simply called “wago”) or terminal blocks. Using WAGO datasheets and HD 60364-5-52, this article shows which connector suits which wire, how much current it carries, and where a joint is allowed in a house at all.
In short
- WAGO 2273: solid wire only, 0.5–2.5 mm², 24 A, 450 V, T60 (datasheet). For junction boxes with solid cable.
- WAGO 221 (lever): solid, stranded and fine-stranded wire; 221-4xx up to 4 mm², 32 A; 221-6xx up to 6 mm², 41 A. For lights where flexible wire is involved.
- Terminal block: on a DIN rail, in the board or plant room, with screw, spring or push-in connection.
- Joints only where accessible: in a box, under a cover – no joints buried in plaster (HD 60364-5-52, 526).
- For all of them: strip length and cross-section per datasheet, wire pushed fully home.
Author: Norbert Madarász
, Managing Director and Partner · Updated: 11 November 2026
WAGO 221, 2273 and terminal blocks: what is the difference?
| Connector | Wire | Cross-section | Current, temperature | Where |
|---|---|---|---|---|
| WAGO 2273 (2–8 poles) | solid only | 0.5–2.5 mm² | 24 A, T60 | junction box, solid cable |
| WAGO 221-4xx (2, 3, 5 poles) | solid, stranded, fine-stranded | 0.2–4 mm² (fine-stranded from 0.14) | 32 A, T85 | lights, mixed wires, junction box |
| WAGO 221-6xx (2, 3, 5 poles) | solid, stranded, fine-stranded | 0.5–6 mm² | 41 A | larger cross-sections |
| Terminal block | by type | by type | per datasheet | DIN rail, board, plant room |
The figures come from WAGO datasheets (IEC/EN ratings, 450 V). “T60” and “T85” mean the connector may be used at ambient temperatures up to 60 or 85 °C – this matters inside luminaires and in warm places.
WAGO 221: lever connector for every wire type
The 221 series is a clamp opened and closed by a lever, with a transparent housing: after inserting the wire you can see whether it is fully home. The 221-412, -413, -415 take two, three and five wires up to 4 mm²; the 221-612, -613, -615 do the same up to 6 mm².
- Fine-stranded wire (luminaire leads, flexible cable) can be connected without a ferrule – the main advantage over the 2273.
- Mixed joints: solid and fine-stranded wires in one connector, which makes it a good choice for lights. On connecting a light: connecting a light fitting.
- The lever reopens, so the joint can be undone; the strip length is given in the datasheet.
WAGO 2273: solid wire only
The 2273 series is a compact push-in connector for solid wire from 0.5 to 2.5 mm². Per the datasheet: 24 A, 450 V, 4 kV impulse voltage, T60, 11 mm strip length. Its small size makes it handy in crowded junction boxes.
- Not for fine-stranded wire: the spring does not hold thin strands reliably. Use a 221 instead.
- Aluminium wire: according to WAGO, solid aluminium can be used, but only with WAGO “Alu-Plus” contact paste and reduced current (16 A on 2.5 mm²). With an old aluminium installation, renewal is usually the better answer: electrical installation.
Terminal blocks: screw, spring or push-in
A terminal block clips onto a DIN rail and is used in distribution boards, plant rooms and control cabinets. DIN-rail terminal blocks are made by WAGO (for example the TOPJOB S family), Phoenix Contact and other manufacturers.
- Screw: the long-established solution; tighten to the manufacturer’s torque and recheck in places with vibration.
- Spring (cage clamp) and push-in: opened without tools or with a screwdriver, they do not loosen; solid wire can be pushed straight into a push-in clamp.
- Main terminals, distribution blocks: for splitting the supply, neutral and protective earth; for larger cross-sections.
In a consumer unit the terminal blocks go on the same rail as the MCBs and RCDs. On boards: distribution board manufacturing; on protective devices: circuit breakers and surge arresters.
Junction boxes: where can a joint be in the wall?
Under section 526 of HD 60364-5-52, every connection must provide durable electrical continuity and adequate mechanical strength and – with a few exceptions (such as joints designed to be buried or compound-filled) – must be accessible for inspection, testing and maintenance. Joints go into an enclosure or box.
- Junction box in the wall or ceiling with a removable cover that stays reachable later (not tiled over, not hidden behind a wardrobe).
- In drywall use hollow-wall boxes; at a light outlet the joint goes into the luminaire’s terminal compartment or a box.
- Twisting and tape do not give a durable, testable joint; the proper solution is a connector or terminal block.
- Manufacturers: junction and flush boxes are made by Kaiser, Kopos and OBO Bettermann among others; the box is chosen for the wall material (brick, concrete, drywall) and the depth needed.
WAGO or terminal block: when to use which?
- Junction box, solid wire: 2273 or 221, depending on the number of wires.
- At a light, fine-stranded wire: 221, or the luminaire’s own terminal.
- Above 4 mm², up to 6 mm²: 221-6xx or a terminal block.
- Board, plant room, control cabinet: DIN-rail terminal blocks, labelled, according to the wiring diagram.
- Always: cross-section and current within the datasheet, wire fully home, joint accessible.
We work with WAGO connectors and OBO products. Before handover the installation is tested, and you receive a test report.
Frequently asked questions
What is the difference between WAGO 221 and 2273?
The 2273 is for solid wire only, 0.5–2.5 mm², up to 24 A. The 221 lever connector takes solid, stranded and fine-stranded wire: 221-4xx up to 4 mm² and 32 A, 221-6xx up to 6 mm² and 41 A (WAGO datasheets).
Are WAGO connectors safe?
Yes, when used within the datasheet: for the right wire type and cross-section, with the given strip length, pushed fully home, and with the joint in a box where it remains accessible.
Can WAGO connectors take fine-stranded wire?
The 221 lever connector can, even without a ferrule. The 2273 is for solid wire only.
WAGO or terminal block in a distribution board?
In a board, DIN-rail terminal blocks are standard, labelled and according to the diagram. WAGO splicing connectors are for junction boxes and lights.
May a joint be plastered over?
No. Under HD 60364-5-52, joints must – with a few exceptions – remain accessible for inspection and maintenance, so they go into a junction box with a cover.
Can aluminium wire be connected with WAGO?
According to WAGO, solid aluminium can go into the 2273 only with “Alu-Plus” contact paste and reduced current. For old aluminium installations we usually recommend renewal.