Distribution board manufacturing in our own workshop, one-off builds to EN 61439
We build distribution boards in our own workshop: one-off units, not series production, for our own installations and for other companies — electricians and contractors — too. Every finished board passes the routine verification required by EN 61439 (MSZ EN 61439 in Hungary) and is handed over with the documentation the standard requires.
What distribution boards do we build?
Custom boards built to the design or the client’s requirements: devices, enclosure, degree of protection and layout are matched to each building and system. Production takes place in our own workshop, so assembly quality, wiring order and labelling are in our hands, not dependent on site conditions.
What does the EN 61439 standard require?
Low-voltage switchgear and controlgear assemblies (distribution boards, control cabinets) are covered by the IEC 61439 series, adopted in Hungary as MSZ EN 61439. Part 1 gives the general rules; further parts are product standards by type of assembly:
| Part | Scope |
|---|---|
| EN 61439-1 | general rules: roles, design verification, routine verification, marking, documentation |
| EN 61439-2 | power switchgear and controlgear assemblies (PSC), typically main and industrial boards, control cabinets |
| EN 61439-3 | distribution boards intended to be operated by ordinary persons (DBO): nominal voltage to earth up to 300 V AC, outgoing circuits up to 125 A, the board up to 250 A |
| EN 61439-4, -5, -6 | construction site assemblies, public network distribution, busbar trunking systems |
The board of a family house or flat, operated by the occupants themselves (circuit breakers, RCDs), usually falls under Part 3. The current edition of IEC 61439-3 is the second edition of 2024.
Who is responsible for what: original and assembly manufacturer
| Role | Who | Duties |
|---|---|---|
| Original manufacturer | the organisation that developed the enclosure, busbar or modular system (usually the enclosure and device maker) | design verification of the system and assembly instructions |
| Assembly manufacturer | the organisation that builds the specific board and is responsible for the finished assembly | assembly to the original manufacturer’s instructions, routine verification of every finished board, marking and documentation |
For the boards we build, we are the assembly manufacturer and responsible for the finished board. An assembly manufacturer who deviates from the original manufacturer’s instructions also takes on the original manufacturer’s duties for that deviation and must repeat the verification — which is why we assemble system components to the manufacturer’s instructions.
Design verification and routine verification: what is the difference?
Design verification shows that the design complies with the standard. It can be done by testing, by comparison with a tested reference design, or by assessment (calculation, design rules). It covers, among others, strength of materials, degree of protection (IP), clearances and creepage distances, protection against electric shock, temperature rise and short-circuit withstand strength.
Routine verification is mandatory on every finished board to detect faults in materials and workmanship. We check:
- degree of protection (IP), clearances and creepage distances;
- protection against electric shock and continuity of the protective circuit;
- that built-in devices match the layout and the assembly instructions;
- internal circuits and connections, tightness of terminals;
- terminals for external conductors against the circuit diagram;
- operation of mechanical actuators;
- dielectric properties (power-frequency test or insulation resistance measurement);
- wiring, operation and interlocks.
What documentation comes with the board?
Every board is handed over with the documentation required by EN 61439:
How is a board built?
- Requirement or design single-line diagram, device list or task description; without a design, it can be part of our electrical design.
- Layout enclosure, degree of protection, arrangement, spare ways, terminals and labelling.
- Production in our workshop assembly to the enclosure and device makers’ instructions.
- Routine verification checks and measurements to the standard, with a report.
- Handover or installation handover with the required documentation; if we also do the installation, mounting and connection on site.
Replacing an old consumer unit
When an old fuse box or outdated consumer unit is replaced, we build the new board in the workshop, so on site only isolation, removing the old board and connecting the new one remain. The replacement usually comes with an RCD, and often with a meter point upgrade or a capacity upgrade.
Devices: in consumer units and small boards we install modular devices from Schneider, Hager, ABB, Eaton, Legrand and Siemens. The major manufacturers also offer enclosures, busbars and covers for consumer units; within one board it pays to use one manufacturer’s system so that busbar, RCDs and MCBs fit together. On markings (C16, 6000) and surge protection: circuit breakers and surge arresters.
Related: Electrical installation · KNX smart home · Meter point upgrade · RCD types · Capacity upgrade
Frequently asked questions
What is EN 61439?
The standard series for low-voltage switchgear and controlgear assemblies (distribution boards, control cabinets). Part 1 gives the general rules, the other parts the requirements by type of assembly; boards operated by ordinary persons (such as a home consumer unit) fall under Part 3.
Who is responsible for a distribution board’s compliance?
The assembly manufacturer, i.e. whoever builds the finished board: they carry out routine verification, fit the nameplate and hand over the documentation. For the boards we build, that is us.
What is routine verification?
The check required on every finished board: degree of protection, clearances and creepage distances, shock protection and protective-circuit continuity, built-in devices and connections, terminals, mechanical operation, insulation and wiring. The results are recorded in a report.
Do you build boards for other electricians and contractors?
Yes, we also build custom boards for other companies from their design or device list, with routine verification and the documentation required by the standard.
Do you build in series?
No, we build one-off units: every board to its own circuit diagram and layout.
Let’s talk about your project.
Tell us what you are planning and we will get back to you within a few days.
Get in touch