RCD (residual current device): types, wiring, which one you need
An RCD switches off when part of the current does not return through the neutral but leaks through a body or to earth. A family house today needs at least a type A, 30 mA device; an inverter heat pump often needs type F or B, and an EV charger type B, or type A with 6 mA DC detection (A-EV, RDC-DD). Connecting it is electrician’s work, with tests and a test report.
In short
- What is an RCD for? It protects against electric shock and earth-fault fires: 30 mA for personal protection, 300 mA for fire protection.
- Which type? Type AC only detects pure sinusoidal fault current; a modern home needs at least type A. Variable-speed appliances need F, three-phase inverters and EV chargers B or A-EV / RDC-DD.
- Single or three phase? A two-pole (2P) RCD for a single-phase circuit, a four-pole (4P) one for three-phase.
- Wiring: the phase(s) and neutral pass through it, the protective earth (PE) does not. It is work inside the distribution board: done by an electrician to the standard, handed over with tests and a test report.
Author: Norbert Madarász
, Managing Director and Partner · Updated: 9 November 2026
What is an RCD for, and what does “FI” mean?
In Hungary and Germany the device is called “FI”, from the German “Fehlerstrom” (fault current); the Hungarian standard name is áram-védőkapcsoló (ÁVK), in English RCD. It constantly compares outgoing and returning current. If the difference reaches the rated residual operating current (IΔn), the circuit switches off within a few tenths of a second.
- 30 mA – personal protection: required by the standard as additional protection for socket-outlets used by ordinary persons, bathrooms and outdoor sockets.
- 100–300 mA – fire protection: against fires caused by earth faults, typically on the supply side, upstream of groups.
- What it does not do: it does not protect against overload or short circuit. That needs a circuit breaker, or an RCBO that combines both.
What types of RCD are there?
The type letter tells you which waveform of fault current the device detects. Each “higher” type also detects what the lower ones do.
| Type | What it detects | Where it belongs |
|---|---|---|
| AC | sinusoidal AC fault current only | resistive loads without electronics (e.g. an old immersion heater); not recommended for new installations |
| A | AC + pulsating DC fault current | general household circuits: sockets, lighting, kitchen, single-phase electronic appliances |
| F | A + mixed-frequency fault current (single-phase variable-speed drive) | inverter washing machine, air conditioner, single-phase heat pump, if the manufacturer asks for it |
| B | F + smooth DC and high-frequency fault current | three-phase inverter equipment, heat pump, EV charger, PV inverter, if the manufacturer requires it |
| A-EV / RDC-DD | type A + monitoring of smooth DC above 6 mA (IEC 62955) | EV charger; many wallboxes have the 6 mA DC detection built in |
The choice of type is always based on the appliance manufacturer’s instructions. If the manual of an inverter appliance requires type B, smooth DC can “blind” an upstream type A RCD.
Type A or type AC RCD?
Almost every household appliance is electronic today: power supplies, LED drivers, inverter motors. Their faults can produce a pulsating DC component, which type AC does not reliably detect. In new or renovated consumer units we therefore install type A RCDs. In Germany type AC is not permitted at all under DIN VDE 0100-530 (531.3.3). We move from A to F or B where the appliance manufacturer asks for it, such as for a heat pump or an EV charger.
Which RCD for a heat pump, pool pump, EV charger, instantaneous water heater or PV inverter?
The table shows the usual starting point. It does not replace the appliance manufacturer’s installation instructions: if the manual specifies a type or a rated residual current, that takes precedence.
| Application | RCD type | Sensitivity | Poles | Note |
|---|---|---|---|---|
| Heat pump, single-phase, with integrated inverter | F (B if the manufacturer requires it) | 30 mA, unless the manufacturer specifies otherwise | 2P | the German VDE 0100-530 table assigns single-phase variable-speed appliances (pumps, air conditioners, heat pumps) to types F and B (ABB) |
| Heat pump, three-phase, with integrated inverter | B | 30 mA, unless the manufacturer specifies otherwise | 4P | four-pole type F devices exist (e.g. ABB F204F), but type F is meant for the fault current of single-phase drives; smooth DC fault current from a three-phase inverter is only detected by type B |
| Heat pump and PV inverter on one shared circuit | not recommended | – | – | we give each its own circuit and its own RCD as its manual specifies; if an upstream RCD also carries the fault current of an appliance that needs type B, it must be type B as well: no type A or F ahead of type B |
| Pool pump (filter or circulation pump) | A; F or B for a variable-speed pump if its manual asks for it | 30 mA | 2P (4P for a three-phase pump) | HD 60364-7-702 (HU: MSZ HD 60364-7-702, DE: DIN VDE 0100-702): in zone 1 the permitted protective measures are SELV, an RCD of not more than 30 mA, or electrical separation; pump manufacturers (e.g. Hayward) require an isolating transformer or an RCD of not more than 30 mA |
| EV charger (wallbox) | B, or A with 6 mA DC detection (A-EV / RDC-DD) | 30 mA | 2P or 4P, depending on the charger | a separate RCD for each connection point (HD 60364-7-722, 722.531.3.101); the same in Hungary and Germany |
| Instantaneous water heater, electric shower | A | 30 mA in a bathroom | 4P for a three-phase heater | in a room with a bath or shower every circuit is protected by an RCD of not more than 30 mA (HD 60364-7-701, 701.411.3.3; HU: MSZ HD 60364-7-701, DE: DIN VDE 0100-701); the RCD’s rated current is matched to the circuit breaker ahead of it, because it does not protect against overload |
| PV inverter without galvanic isolation (transformerless) | B, or A if the manufacturer declares that the inverter cannot feed DC fault current | as the manufacturer specifies; some (e.g. SMA) ask for 100 mA or more | 2P (single-phase), 4P (three-phase) | IEC 60364-7-712 (HU: MSZ HD 60364-7-712, DE: DIN VDE 0100-712): type B, unless the inverter by design cannot feed DC residual current; SMA confirms this for many models in a manufacturer’s declaration, while some of its manuals ask for an RCD of at least 100 mA, so a 30 mA device may trip unnecessarily |
| Washing machine, dryer (inverter) | F | 30 mA | 2P | ABB recommends type F for washing-machine, dryer and kitchen socket circuits; the socket needs 30 mA anyway |
| Air conditioner (single-phase inverter) | F, or B if the manufacturer requires it | 30 mA, unless the manufacturer specifies otherwise | 2P | a single-phase variable-speed appliance, like the single-phase heat pump |
What does the Hungarian standard require?
- MSZ HD 60364-4-41 (protection against electric shock), 411.3.3: socket-outlets for general use by ordinary persons are protected by an RCD of not more than 30 mA. The 2005 IEC edition required this up to 20 A, the newer HD edition up to 32 A.
- MSZ HD 60364-5-53: selection and erection of protective devices; this governs type and selectivity.
- MSZ HD 60364-7-722 (supplies for electric vehicles), 722.531.3.101: each connection point needs its own RCD, at least type A, not more than 30 mA, and protection against DC fault current: type B, or type A plus a device that disconnects at DC fault current above 6 mA.
Single-phase or 3-phase RCDs: what is the difference?
A single-phase RCD is two-pole (2P): phase and neutral pass through it. A three-phase one is four-pole (4P): L1, L2, L3 and N. The same 4P device can protect a three-phase load (e.g. hob, heat pump) and several single-phase circuits split across the phases.
Using a three-phase RCD on a single phase
This is the manufacturer’s call, not the installer’s. The test-button circuit is wired between specific poles inside the device, and some types need 400 V for it to work. Schneider Electric, for example, states that its Acti 9 four-pole RCCBs cannot be used single-phase because the test circuit requires 400 V. Other manufacturers specify which terminals to use. For a single-phase circuit the clean solution is a 2P device.
Three-phase (4-pole) RCD and type B RCD: what to watch for
- Type B also detects smooth DC fault current, on top of the type F waveforms, and high-frequency current up to about 2 kHz; type B+ goes up to 20 kHz (ABB). It is needed where a three-phase inverter, an EV charger or a PV inverter can produce smooth DC fault current.
- No type A or F ahead of type B: smooth DC fault current can impair an upstream type A or F RCD, so every upstream RCD that carries the same fault current must also be type B (DIN VDE 0100-530, ABB).
- 4P does not automatically mean type B: four-pole RCDs are made in types AC, A, F and B. The load decides the type, the supply decides the number of poles.
- Leakage current adds up: under DIN VDE 0100-530:2018 the total operational leakage current downstream of an RCD should not exceed 0.3 × its rated residual current, i.e. 9 mA on a 30 mA device; 5–10 electronic devices can already reach this (ABB).
- How many circuits per RCD (Germany): the German planning standard DIN 18015-1 allows at most six final circuits after a four-pole RCD and at most two after a two-pole one. This is a German rule; in Hungary we also split the circuits across several RCDs.
- Price: type B is considerably more expensive than type A; see the indicative prices in the table below.
Several RCDs: per circuit or per group?
A single RCD for the whole house is a poor solution: one faulty appliance switches everything off, fridge and alarm included, and the normal leakage currents of many appliances add up. A good consumer unit has several RCDs:
- Per group: one RCD ahead of 2–4 circuits (e.g. ground-floor sockets, upstairs sockets, kitchen, bathroom), so a fault only switches off one part.
- Per circuit: a separate RCD or RCBO for important and sensitive loads: EV charger, heat pump, outdoor sockets, fridge, IT.
- Selectivity: if there is also a 300 mA fire-protection RCD at the supply, it should be type S (selective, time-delayed), so the 30 mA device trips first and the whole house does not go dark.
- Neutrals must not be mixed: each circuit’s neutral may only pass through its own RCD. If the neutrals of two RCDs touch, both trip without reason. This is the most common fault in consumer units extended later.
How is an RCD connected?
The principle is simple, the execution is not. The incoming phase(s) and neutral go to the upper terminals, the phases and neutrals of the protected circuits to the lower terminals. The protective earth (PE) does not pass through the RCD; it goes to the earth bar. Downstream of the RCD, the circuit’s neutral must not touch the common neutral bar or PE.
More: Electrical installation · EV charger installation · Heat pump electrical connection
Which RCD brand is better?
Every major manufacturer offers RCDs, among them Schneider Electric, Legrand, Hager, ABB, Eaton and Siemens, as well as Schrack and Tracon. The brand does not decide, the datasheet does:
- type (AC, A, F, B, A-EV) to suit the load, as described above;
- sensitivity (30 mA for personal protection) and rated current (for example 25 or 40 A);
- number of poles (2P or 4P) and standard: RCD to EN 61008-1, RCBO to EN 61009-1;
- fit with the busbar of the board and the MCBs next to it, which is why it pays to use one manufacturer within one board.
We work with Schneider, Legrand, Hager, ABB, Eaton and Siemens devices. On MCBs and surge arresters: Circuit breakers and surge arresters
How much does an RCD cost?
The device price depends on type and number of poles; the labour for connecting it weighs more if the board has to be rearranged.
| Device (30 mA) | Market example | Web-shop price |
|---|---|---|
| Single-phase, 2P, 40 A, type A | Siemens 5SV3314-6 | approx. HUF 17,300 |
| Three-phase, 4P, 40 A, type A | Legrand 402075, Eaton PF6-40/4/003-A | approx. HUF 15,500–24,000 |
| Three-phase, 4P, 40 A, type AC | low-cost unbranded devices | from approx. HUF 8,000 |
| Type B, 2P or 4P | brand manufacturers | from approx. HUF 90,000 (e.g. ABB F204B-40/0.03, Voltus: approx. €233) |
| Installation labour | MDRSZ Elektro | quoted after a site survey |
Source: Árgép price comparison, October 2026; gross web-shop prices without shipping, subject to frequent change.
Related articles from our knowledge base
What the standard allows in zones 0, 1 and 2, which IP rating you need, where switches go, and good light at the mirror.
Read →What C16 and 6000 mean, how MCBs are sized, when a T1+T2 arrester is needed, and what to check between brands.
Read →Price installed, power, built-in protection, load management, solar charging and app – from manufacturer datasheets, from an installer’s view.
Read →Frequently asked questions
What is an RCD for?
It switches the circuit off when part of the current leaks through a body or to earth. A 30 mA RCD protects against electric shock, a 300 mA one against earth-fault fires. It does not protect against overload or short circuit; that needs a circuit breaker.
Type A or type AC RCD?
Type A for a modern home. Type AC does not reliably detect the pulsating DC fault current of electronic appliances. For inverter heat pumps and EV chargers the manufacturer often requires type F or B.
Which RCD does an EV charger need?
Its own 30 mA RCD that also protects against DC fault current: type B, or type A with 6 mA DC detection (A-EV, RDC-DD). Many wallboxes have this detection built in; we check it on the charger’s datasheet.
Why does the RCD trip?
Because of a real insulation fault (a damp outdoor socket, a faulty appliance), the added-up leakage of many appliances, or because the neutrals of two circuits touch in the board. If it can be reset but trips again, have an electrician locate the fault by measurement.
Can a layperson connect an RCD?
We do not recommend it. Work in the distribution board is an electrician’s job, and a wrongly connected RCD does not protect. After connection, instrument tests and a test report are needed.
30 mA or 300 mA RCD?
In a home, 30 mA ahead of the circuits, because that protects against electric shock. 300 mA is for fire protection, and if used at the supply it should be selective (type S).
How much does an RCD cost?
In web shops a 2P, 40 A, type A RCD is about HUF 17,000, a 4P type A about HUF 15,500–24,000 (Árgép, October 2026). Type B is considerably more expensive. Installation labour comes on top.
Which RCD does a heat pump with an inverter need?
Usually a 30 mA type F for a single-phase unit and a 30 mA type B for a three-phase one, unless the manufacturer’s manual specifies otherwise; the manual takes precedence. No type A or F RCD may sit ahead of a type B one.
Which RCD for a pool pump?
A 30 mA RCD: type A for a fixed-speed pump, type F or B for a variable-speed pump if its manual asks for it. In zone 1 of the pool, HD 60364-7-702 (DIN VDE 0100-702 in Germany, MSZ HD 60364-7-702 in Hungary) only allows SELV, an RCD of not more than 30 mA, or electrical separation.
Does an instantaneous water heater need an RCD?
In a room with a bath or shower, yes: every circuit there is protected by an RCD of not more than 30 mA (HD 60364-7-701, 701.411.3.3). A three-phase heater needs a four-pole RCD rated to suit its circuit breaker.